Description:
Rubber Sheathed Mine Flexible Cable
rubber insulated cable,
flexible rubber power cable,
rubber sheathed mine cable,
Rubber Sheathed Flexible Cable

1. Usage:Rubber sheath flexible cable is suitable for rated AC vo1tage 450/750V or below domestic applies, power-operated tools and various portable electric Equipments
2. Working temperature:
1) YZ model flexible cable rated voltage Uo/U is 300/500V, YC model is 450/750V
2) Long time allow working temperature of wire core is not more than 650C, or 900C, or 1050C. ( It depend on the jacket material.)
3) W model flexible power cable has the property of durability and suitable for outdoor touching of greasy dirt
4) ZR model flexible rubber cable has the property of fire-resistance
Construction:
Rubber Sheathed Mine Flexible Cable
|
General Rubber Flex Cable Construction |
|
|
Conductor |
Finest annealed bare copper Class 5/6 |
|
Core |
Single, multi core |
|
Jacket |
Rubber/ TPE/CPE/EPDM/ Silicone |
What's the Technical Parameters of H07 RNF Rubber Cable?
What's the Technical Parameters of General flex Rubber Cable?
|
Model |
Name |
Rated Voltage(V) |
Section Area(mm2) |
No. of Cores |
Usage |
|
YQ,YQW |
Light model rubber sheath flexible cable |
300/300 |
0.30.5 |
2,3 |
Used for light portable electric equipment and tools |
|
IEC60245-53(YZ) YZ |
Middle model rubber sheath flexible cable |
300/500 |
0.75--6 |
2,3,4,5 |
Used for various portable electric equipment and tools |
|
IEC60245-57(YZW) YZW |
|||||
|
YC |
Heavy model rubber sheath flexible cable |
450/750 |
1.5--400 |
1 |
Used for various portable electric equipment which can bear large mechanical force effect |
|
1.5--95 |
2 |
||||
|
1.5--150 |
3 |
||||
|
IEC60245-66 YCW |
1.5--150 |
4 |
|||
|
2.515 |
3+1 |
||||
|
+ |
|||||
|
1.5--50 |
|||||
|
1.5--25 |
5 |
Rubber Sheathed Mine Flexible Cable Appliance:
1) Conductor: class 5 tinned copper
2) Sectional area: power core, 25-150mm2; earth core, 16-50mm2; monitoring core, 2.5mm2
3) Conductor screen: extruded or lapped semi-conducting material
4) Insulation: rubber
5) Insulation screen: extruded semi-conducting material + braided metal / fiber
6) Inner Sheath: rubber
7) Monitoring layer: lapped semi-conducting material + monitoring cores + lapped semi-conducting material
8) Outer sheath: rubber
9) Min. bending radius: 6 times cable diameter
10) Max. conductor DC resistance at 20°c:
Rubber Sheathed Mine Flexible Cable - Technology Parameters
|
Core numbers |
Wire core of |
Insulator |
Normal insulated mm |
Outer diam |
Outer diam |
Conductor resistance at 20≤Ω/Km |
|
|
Cu core |
Tinning cu-core |
||||||
|
2×0.75 |
24/0.20 |
0.6 |
0.8 |
6.28 |
7.22 |
26 |
26.7 |
|
2×1.. |
32/0.20 |
0.6 |
0.9 |
6.84 |
7.87 |
19.5 |
20 |
|
2×1.5 |
30/0.25 |
0.7 |
1 |
8 |
9.2 |
13.3 |
13.7 |
|
2×2.5 |
49/0.25 |
0.8 |
1.1 |
9.2 |
10.58 |
7.98 |
8.21 |
|
3×0.75 |
24/0.20 |
0.6 |
0.9 |
6.84 |
7.87 |
26 |
26.7 |
|
3×1.00 |
32/0.20 |
0.6 |
0.9 |
7.23 |
8.31 |
19.5 |
20 |
|
3×1.5 |
30/0.25 |
0.7 |
1 |
8.46 |
9.73 |
13.3 |
13.7 |
|
3×2.5 |
49/0.25 |
0.8 |
1.1 |
9.96 |
11.45 |
7.98 |
8.21 |
|
4×0.75 |
24/0.20 |
0.6 |
0.9 |
7.48 |
8.58 |
26 |
26.7 |
|
4×1.00 |
32/0.20 |
0.6 |
0.9 |
7.88 |
9.06 |
19.5 |
20 |
|
4×1.5 |
30/0.25 |
0.7 |
1 |
9.44 |
10.86 |
13.3 |
13.7 |
|
4×2.5 |
49/0.25 |
0.8 |
1.2 |
11.09 |
12.75 |
7.98 |
8.21 |
|
2×4 |
56/0.30 |
1 |
1.8 |
12.8 |
14.72 |
4.95 |
5.09 |
|
2×6 |
84/0.30 |
1 |
2 |
15.2 |
17.48 |
3.3 |
3.39 |
|
2×10 |
84/0.40 |
1.2 |
3.1 |
20.2 |
23.23 |
1.91 |
1.95 |
|
2×16 |
126/0.40 |
1.2 |
3.3 |
22.8 |
26.22 |
1.21 |
1.24 |
|
2×25 |
196/0.40 |
1.4 |
3.6 |
27 |
31.05 |
0.78 |
0.795 |
|
2×35 |
276/0.40 |
1.4 |
3.9 |
30.4 |
34.96 |
0.554 |
0.565 |
|
3×4 |
56/0.30 |
1 |
1.9 |
13.7 |
15.75 |
4.95 |
5.09 |
|
3×6 |
84/0.30 |
1 |
2.1 |
16.3 |
18.74 |
3.3 |
3.39 |